Anchoring clamp for self-supporting system ЗАН-4Question
Can an anchoring clamp for self-supporting system ЗАН-4 be used as an in-between connector?
Answer
Yes, this clamp is universal, so it can be used as an in-between connector. To do so first untighten the fixation part and turn the cap to 90°. So in result, you will get the support that holds a four-cable ABC.
Anchoring pole bracket КАБ-25Question
Can clamps be fixed with an anchoring pole bracket КАБ-25?
Answer
This bracket was designed for a working load of 0.8 kN. It is better to match loads of the clamp and a bracket, so, in this case, the best choice combination of КАБ-25 and ЗАБ-25.
Helical ties ВСQuestion
With what type of cable should I use helical ties ВС made by KBT?
Answer
The helical ties are designed for the fixation of SAX cables to pin-type insulators and support insulators. In case of need, these ties can be also used for the installation of non-insulated cables.
Ferrules ГСИ-А, ГСИ-Ф and ГСИ-НQuestion
Are insulated ferrules ГСИ-А, ГСИ-Ф and ГСИ-Н interchangeable and be used one instead of another?
Answer
No, they are designed for different purposes. The main purpose of these three types is a leak-proof connection of insulated. ГСИ-А are designed for customer connections from the mainline in cross-section range from 6 to 25 mm². They are short as the load is not very big, they have tensile strength s no less than 60% of the strength of the conductor. ГСИ-Ф are sued for connection of phase conductors in cross sections range from 35 to 150 mm². They are longer than ГСИ-А. Tensile strength of ГСИ-Ф is no less than 60% of the strength of the conductor’ strength. ГСИ-Н are used for connection of zero lines, that bear the most load.
СБТК setsQuestion
Can a set of a shear-off bolt connector with an insulation cuff, that is called СБТК, be used in the same cases as leak-proof insulated ferrules?
Answer
No, as these two variants have different designs.
Bolt connectors are fixed with the help of shear-off bolts, whereas insulated ferrules are fixed by crimping. Branch, phase and neutral ferrules have an inbuilt plastic case designed for protection from most. The set СБТК has heat shrinkable sleeves for this purpose. The CБТК set can be used as a substitute for branch and phase ferrules, but not neutral ferrules because neutral ferrules bear axial load, but shear off bolt connectors cannot do this task.
НБТК setsQuestion
Can I use a НБТК set instead of insulated ring terminals НИАМ?
Answer
НБТК set consists of shear-off-head bolts lugs and heat-shrinkable cuffs. We recommend using a bimetallic washer ШАМ and conductive paste or better results.
Buckles БМ-20 nd brackets СМ-20Question
Stainless steel buckles БМ-20 are more expensive than stainless steel brackets СМ-20? Does it worth to pay more?
Answer
Brackets and buckles are used for the fixation of steel band on different bearings. But still, they are designed for different purposes. Brackets are designed for fixation of the band on intermediate bearings, buckles- on anchor bearings. The thickness of buckles is more than the thickness of brackets. Moreover, buckles have special teeth for better and more reliable fixation. So every time before you calculate the cost, you should be aware of the load you deal with.
Piercing clamp ЗПО made by KBT for the connection of two cables under tensionQuestion
Can I use a piercing clamp ЗПО made by KBT for the connection of two cables under tension?
Answer
No, you cannot use a piercing clamp for connection of cables under tension. The clamp for not designed for any load. We recommend using insulated ferrules for the connection of cables under tension. They were designed for this purpose.